Triol AK06 Flexible Cabinet
Place an orderDistinctive benefits
-20°С … +60°С
Operating temperature range
NEMA4
Enclosure
Built-in
Output filter provides THDi and THDu output <5%
Cabinets
Designed to integrate third-party variable frequency drives
About product
Versatile solution with NEMA4
Variable Speed Drive AK06 line FC is a versatile NEMA4 enclosure solution which complies with NEMA 250-2014 standard. Enclosures of FC line are specially designed to have the possibility to integrate thirdparty variable speed drives into their cabinet.
Output filter, highly protected enclosure
FC line cabinet includes an input switching and protection equipment, an output filter, and an air-to-air heat exchanger for use in submersible and surface pumps for oil-producing and other industries. Input harmonic filter can be integrated into the cabinet of FC line. The highly protected enclosure and built-in power bay locking system ensure the reliable and safe use of the cabinet in outdoor conditions.
Specifications
Parameter
|
Value
|
---|---|
Power supply, V
|
V 3х380% 15% / 3х480 (-15% ... + 10%)
|
Input frequency, Hz
|
50±1 Hz and/or 60±1 Hz
|
Rated output current, A
|
100 – 675
|
characteristics
|
120% of rated value within 60 sec
|
Change of frequency task increment, Hz
|
Hz 0,1
|
Level of distortion in the output current THDi,%
|
% <5%
|
Level of distortion in the output voltage THDi,%
|
<5%
|
Level of distortion of current in the input network
|
<5% in the load range from 70% to 100%
|
DC bus choke
|
Built-in
|
Input passive filter
|
Option, Built-in
|
Sine filter
|
Built-in
|
PWM frequency, kHz
|
kHz> = 2,5
|
HMI
|
Process controller integration as per customer request
|
Local alarm
|
Optional
|
Operator Control Voltage
|
Optional: specified upon order
|
Enclosure protection
|
NEMA4
|
Material of enclosure
|
Carbon steel
|
Operating temperature
|
20°С … +55°С (with decrease of output power)
|
Relative humidity
|
95%
|
Cooling type
|
Air forced
|